Description
IEC / EN 61000-4-6 specifies the design and performance of a range of coupling / decoupling networks (CDNs). Each CDN is specific to the type of cable and the intended signal carried on the cable. Teseq offers an extensive range of CDNs which fully comply with the requirements of the standard and provide a simple and reliable method of injecting RF energy into the equipment under test (EUT).
Teseq CDN M1116S Features:
- M116S Coupling/Decoupling Network
- Calibration Adapter
- 4mm banana to 4mm banana adapter
- Carrying Case
- User Manual
- Calibration certificate
- 10% off Calibration Service for life
Videos
Custom Field
Coupling BNC 50 Ω
Current Rating 16 A, (25 A for 1 s PE line test)
Frequency Range 150 kHz to 230 MHz (300 MHz)
Insertion Loss less than 0.1 dB
RF Input Voltage less than 20 V, refers to 33 V test level in 300 Ω
Standards Met IEC / EN 61000-4-6
Voltage Division Factor 150 kHz to 80 MHz: 9.5 dB ±1 dB
80 MHz to 230 MHz: 9.5 dB +3 dB / -2 dB