Telecom Testing Generators

(Showing 9 of 9)

Telecom networks and connected telecom systems and devices are subject to lightning strikes and other disturbances and therefore require an effective and carefully selected protection. Designed to meet the various requirements laid out by ITU, FCC and Telcordia/Bellcore. The EMC Shop stocks all a wide variety of Telecom Testing Generators for compliance and pre-compliance testing. Rent or buy Telecom Testing Generators for individual tests or multifunction generators to complete an assortment of tests in a compact solution. Most systems can be easily upgraded to include additional tests as required.

Get Application Support, Pricing, Lead Time and More: CONTACT FORM



Telecom Testing Generators are typically benchtop, but heavy equipment. When doing testing on three phase power lines systems usually require much larger coupling/decoupling networks which substantially increase system size. EM test environments with ground planes with connections to earth are required to safely use transient generators.

  • EM Test

    SKU: sku-776

    Rent EM Test TSS 500M2F Telecom Surge Simulator for FCC Part 68

    Weight: approx. 35kg
    Application/Test Type: Test levels as per FCC part 68
    Coupling: Telecom ports: Tip to Ground, Ring to Ground, Tip and Ring to Ground Power ports 250V/16A: L toN, L to PE, N to PE , L+N to PE
    Dimensions: 19“ / 6HU,
    Output Current: 64A – 1,000A (power line) 20 – 200A per wire (surge A)
    Outputs: 4 mm banana socket
    Polarity: pos / neg / alternate
    Rise time: Less than 2 us
    Telecom Surge: As per FCC part 68, Pulse B, IEC 61000-4-5, ITU and ETSI recommendations
    Test Voltage: 160V – 2,500V ± 10% (power line) 160V – 1,500V ± 10% (surge A)
    Trigger of bursts: Automatic pulse release
  • EM Test

    SKU: sku-403

    EM Test TSS 500N10 Telecom Surge Generator ITU-T for Enhanced Level Testing up to 10 kV

    Weight: approx. 37.1 kg (81.8 lbs.)
    AC Power Adapter: Supply voltage 115/230 V +10/-15%
    Dimensions: 19"/9 HU, 420 mm x 448 mm x 500 mm
    Energy Storage Capacitor: 1 uF (Pulse 1.2/50 us) 20 uF (Pulse 10/700 μs) 20 uF (Surge Pulse B)
    Front Time: 1 us ± 30% (Pulse 1.2/50 us) 10 us ± 30% (Pulse 10/700 μs) 9 us ± 30% (Surge Pulse B)
    Pulse Duration: 50 us ± 20% (Pulse 1.2/50 us) 700 us ± 20% (Pulse 10/700 us) 720 us ± 20% (Surge Pulse B)
    Standards Met: IEC 61000-4-5 ITU-T K.17 ITU-T K.20 ITU-T K.21 ITU-T K.28 ITU-T K.45 (and more)
    Telecom Surge: As per FCC part 68, Pulse B, IEC 61000-4-5, ITU and ETSI recommendations
    Test Voltage: 500 V - 10,000 V ± 10%
  • Teseq

    SKU: sku-182

    Rent Teseq NSG 3060 for Surge, EFT/Burst, Dips/Interrupts, and Ring Wave up to 6.6 kV

    1 review

    Test Capabilities: Combination Wave Surge Immunity , EFT/Burst, Dips Interrupts & Variations
    Standards Met: IEC/EN 61000-4-4, IEC/EN 61000-4-5, IEC/EN 61000-4-11, IEC/EN 61000-4-29
    Applications: CE Marking, Medical Devices, Industrial Machinery, Electronics & IT
    Max EUT AC Voltage (w/ Built in CDN): 264 Volts
    Max EUT AC Current (w/ Built in CDN): 16 Amps
    Max EUT DC Voltage (w/ Built in CDN): 220 Volts
    Max EUT DC Current (w/ Built in CDN): 10 Amps
    EFT/Burst Pulse Output Capability: ±200 V to 4.8 kV (in 1 V steps) - open circuit±100 V to 2.4 kV ±100 A to 2.2 kA
    Combination/Wave Surge Output Capability: ±200 V to 4.4 kV (in 1 V steps)
    External Coupling: Data Lines (EFT & Surge), 3PH EUT
    Coupling: ANSI / IEC / external
    Coupling-2: ANSI / IEC / external
    Dips, Interrupts & Variations: From EUT voltage input to 0 V, 0%
    Impedance: 12/30/200 Ω
    Phase synchronization: asynchronous, synchronous 0 to 359º (in 1º steps)
    Phase synchronization-2: asynchronous, synchronous 0 to 359º (in 1º steps)
    Phase synchronization-3: asynchronous, synchronous 0 to 359º (in 1º steps)
    Polarity: positive / negative / alternate
    Polarity-2: positive / negative / alternate
    Pulse current (short circuit): ±16.6 to ±550 A, ±10%; ±6.6 to ±220 A, ±10%; ±1 to ±33 A, ±10%
    Pulse repetition: 10* s, up to 600 s (in 1 s steps) * see datasheet for derating info
    Pulse voltage (open circuit): ± 200 V to 6.6 kV (in 1 V steps)
    Repetition time: 40 μs to 35 min, 1 to 99’999 cycles
    Test duration: 1 s to 1000 h
    Test duration-2: 1 s to 70’000 min, 1 to 99’999 events, continuous
    Test duration-3: 1 to 9999 pulses, continuous
    Burst (EFT) 5/50 ns: Pulse conforms to IEC/EN 61000-4-4
    Burst frequency: 100 Hz to 1000 kHz
    Burst time: 1 μs to 1999 s, single pulse, continuous
    Combination wave pulse 1, 2/50 - 8/20 μs (Hybrid-Surge pulse): Pulse conforms to IEC/EN 61000-4-5
    Coupling-3: ANSI / IEC / external
    Dips, Interrupts & Variations-2: Conforms to IEC/EN 61000-4-11, IEC/EN 61000-4-29
    Event time: 20 µs to 1999 s, 1 to 300 cycles or 1 to 3’000 1/10 cycles
    Impedance-2: 2/12 Ω
    Phase synchronization-4: asynchronous, synchronous 0 to 359º (in 1º steps)
    Polarity-3: positive / negative / alternate
    Pulse amplitude: ±200 V to 4.8 kV (in 1 V steps) - open circuit; ±100 V to 2.4 kV (50 Ω matching system)
    Pulse current (short circuit)-2: ±100 A to 3.3 kA
    Pulse repetition-2: 10* s, up to 600 s (in 1 s steps) * see datasheet for derating info
    Pulse voltage (open circuit)-2: ±200 V to 6.6 kV (in 1 V steps)
    Repetition time-2: 1 ms to 4200 s (70 min)
    Ringwave 0.5 μs/100 kHz: Pulse conforms to IEC/EN 61000-4-12 and ANSI (IEEE) C62.41
    Switching times: 1 to 5 μs (100 Ω load)
    Test duration-4: 1 to 9999 pulses, continuous
    Uvar with optional variac: depending on model (VAR 3005)
    Uvar with step transformer: 0, 40, 70, 80% (INA 650x)
    Typically In Stock
  • 3ctest

    SKU: sku-333

    3ctest CWS 600CT Combination Wave & Telecom Surge Simulator, 1.2/50us 8/20us 10/700us 5/320us

    Polarity: Positive, Negative or Alternate
    Weight: Approx 15 kg (33 lbs)
    Combination wave pulse 1, 2/50 - 8/20 μs (Hybrid-Surge pulse): Pulse conforms to IEC/EN 61000-4-5
    Counter: 1-999
    Coupling: Optional for external SPN series CDN's
    Dimensions: 19 inch/6u
    Frequency Range: 50/60Hz±5%
    Front Time: Voltage: 10us±20%, time to half value: 700us±20%;
    Impedance: 2 phm, Optional 12 ohm and 500 ohm
    Mains & EUT Connections: 4mm banana plug
    Output Current: Front time: 5us±20%, time to half value: 320us±20%
    Polarity-2: Positive, Negative and Alternating
    Pulse current (short circuit): 0.15 kA–3.0kA ±10% (2ohm)
    Pulse Duration: 11s-99s (shortest depends on test voltage)
    Pulse repetition: 1-999
    Pulse voltage (open circuit): 0.3kV–6.0kV ±10%
    RF Connector: BNC, 5VTTL
    Standards Met: UL 1449, ANSI C62.41, IEC 61000-4-5, EN & IEC 60255-5, GB/T 17626.5
    Telecom Surge: As per FCC part 68, Pulse B, IEC 61000-4-5, ITU and ETSI recommendations
    Test duration: 6s-99s
    Test Voltage: 0.2kV–6.0kV,±10%
    Transfer Impedance: 15ohm, 40ohm (automatic switch)
    Voltage Rating: AC 110V/220V , ±10%,
  • 3ctest

    SKU: sku-330

    3ctest CWS 600T 10/700us Telecom Wave Surge Simulator for IEC 61000-4-5

    Weight: Approx 15 kg (33 lbs)
    Counter: 1-999
    Dimensions: 19 inch/6u
    Frequency Range: 50/60Hz±5%
    Front Time: Voltage: 10us±20%, time to half value: 700us±20%;
    Mains & EUT Connections: 4mm banana plug
    Output Current: Front time: 5us±20%, time to half value: 320us±20%
    Polarity: Positive, Negative or Alternate
    Pulse Duration: 11s-99s (shortest depends on test voltage)
    RF Connector: BNC, 5VTTL
    Standards Met: IEC 61000-4-5 and ITUETSI
    Telecom Surge: As per FCC part 68, Pulse B, IEC 61000-4-5, ITU and ETSI recommendations
    Test Voltage: 0.2kV–6.0kV,±10%
    Transfer Impedance: 15ohm, 40ohm (automatic switch)
    Voltage Rating: AC 110V/220V , ±10%,